One Way Slab Design – How To Design One Way Slab
|In this article, I will discuss how to design One way slab with example.
What Is One Way Slab?
When a slab is supported on all four sides and the ratio of long span to short span is equal or greater than two, it will be considered as one way slab. The load on the slab is carried by the short span in one direction. However main reinforcement bar and distribution bar in transverse direction.
Longer span (l)/Shorter span (b) ≥ 2
ACI Code Specifications For One Way Slab Design:
1. Minimum Slab Thickness:
To control deflection, ACI Code 9.5.2.1 specifies minimum thickness values for one-way solid slabs.
2. Span:
According to ACI code 8.7.1 If the slab rests freely on its supports, the span length may be taken as equal to the clear span plus the depth of the slab but need not exceed the distance between centers of supports.
3. Bar Spacing:
The lateral spacing of the flexural bars should not exceed 3 times the thickness h or 18 inch
according to ACI code 7.6.5 The lateral spacing of temperature and shrinkage reinforcement should not be placed farther apart than 5 times the slab thickness or 18 inch according to ACI code 7.12.2
4. Maximum Reinforcement Ratio:
Reinforcement ratio is the ratio of reinforcement area to gross concrete area based on total
depth of slab. One-way solid slabs are designed as rectangular sections subjected to shear and moment. Thus, the maximum reinforcement ratio corresponds to a net tensile strain in the
reinforcement, €t of 0.004
5. Minimum Reinforcement Ratio:
a) For temperature and shrinkage reinforcement :
According to ACI Code 7.12.2.1
Slabs with Grade 40 or 50 deformed bars –> 0.0020
Slabs with Grade 60 deformed bars –> 0.0018
Slabs where reinforcement with yield strength Exceeding 60000 psi- ->( 0.0018 x 60000/fy)
b) For flexural reinforcement :
According to ACI Code 10.5.4, the minimum flexural reinforcement is not to be less than the shrinkage reinforcement, or 0.0018
Example Problem:
A reinforced concrete slab is built integrally with its supports and consists of equal span of 15 ft. The service live load is 100 psf and 4000 psi concrete is specified for use with steel with a yield stress equal to 60000 psi. Design the slab following the provisions of the ACI code.
Thickness Estimation:
For being both ends continuous minimum slab thickness = L/28 =(15 x 120)/28= 6.43 in.
Let a trial thickness of 6.50 in.
Load Calculation:
Consider only a 1 ft width of beam.
Dead load = 150 x (6.50/12)) = 81 psf
Live load = 100 psf
Factored DL and LL ={81+1.2+(100 x 1.6)} =257 psf
Determine Maximum Moments:
Factored moments at critical sections by ACI code :
At interior support : -M=1/9 x 0.257 x 152 = 6.43 k-ft
At midspan : +M=1/14 x 0.257 x 152 = 4.13 k-ft
At exterior support : -M=1/24 x 0.257 x 152 = 2.41 k-ft
Mmax = 6.43 k-ft
=0.85 x 0.85 x 4/60 x 0.003/(0.003+0.004)
= 0.021
Now,
= 2.64 in
Check For Availability Of Thickness:
As ‘d’ is less than the effective depth of (6.50-1.00) = 5.50 in, the thickness of 6.50 in
can be adopted.
Reinforcement Calculation:
Let, a = 1 inch
At interior support:
Checking the assumed depth of a by
Similarly at Midspan:
As = (4.13 x 12)/(0.90 x 60 x 5.29) = 0.17 in²
At Exterior support:
As = (2.41 x 12)/(0.90 x 60 x 5.29) = 0.10 in²
Minimum Reinforcement:
As = 0.0018 x 12 x 6.50 = 0.14 in²
So we have to provide this amount of reinforcement where As is less than 0.14 in².
Shrinkage Reinforcement:
Minimum reinforcement for shrinkage and temperature is
As = 0.0018 x 12 x 6.50 = 0.14 in²
Factored DL and LL should be ={(81×1.2)+(100×1.6)} =257 psf
Sure looks good and simplified.
Please tell me about the length of 152 feet in moment calculations
Good design. And explaination
all are good design and detailing explanation in the one way slab.
I am understanding all things ,but one thing is left for me
pls show me how can I derive the calculation ratio for the long span to short span is greater or equal two.